Calculator
Choose what you want to calculate. Use line-to-line voltage for standard three phase calculations.
Results
- Waiting for input—
Calculate current (amps), active power (kW), apparent power (kVA), and reactive power (kVAR) in a balanced 3-phase system. Then use the full guide below for formulas, sizing strategy, and practical design checks.
Choose what you want to calculate. Use line-to-line voltage for standard three phase calculations.
Results
Three phase load calculation is the process of determining electrical power, current, and capacity requirements in a 3-phase AC system. It is a core task in electrical design for factories, commercial buildings, pumps, compressors, HVAC units, and motor-driven systems. A proper three phase calculation helps you choose the correct cable size, protective devices, transformer rating, and generator capacity while avoiding nuisance tripping and energy losses.
In a balanced three phase circuit, the total power is distributed across three sinusoidal waveforms separated by 120 degrees. Because of this phase relationship, three phase systems can transfer more power with less conductor material than single phase systems, which is why they are standard for medium and large loads.
The most used formula is for active power in kilowatts:
Where:
Other essential formulas:
Example 1: Find current from power
A 30 kW load runs at 415 V, PF = 0.9. Find line current.
Example 2: Find kW from current
A machine draws 60 A at 400 V with PF = 0.85. Find active power.
Example 3: Find kVA and kVAR
Given 415 V and 80 A:
If measured real power is 46 kW:
Motor circuits need additional care because starting current can be multiple times full-load current (FLC). For direct-on-line starting, inrush can often reach 5 to 8 times FLC. This affects voltage drop, breaker selection, and generator sizing. Even if the steady-state current is acceptable, the starting condition may require a larger feeder or a different starter method.
Three phase load calculation is only the first step. The final design usually includes:
| Design Item | Input from Load Calculation | Typical Engineering Check |
|---|---|---|
| Feeder Current | Calculated line current (A) | Continuous load factor and demand margin |
| Cable Size | Design current + route length | Ampacity, voltage drop, short-circuit withstand |
| Breaker Rating | Running and starting current | Trip curve coordination and selectivity |
| Transformer Size | Total kVA and PF | Derating, harmonics, future capacity |
| Capacitor Bank | Existing kW and target PF | Required kVAR correction and switching steps |
Low power factor raises current for the same useful power, increasing I²R losses, cable heating, and potential utility penalties. By improving PF with capacitor banks or active correction, many systems reduce current demand, free up transformer capacity, and improve voltage stability. Any PF correction project should include harmonic analysis and staged control to prevent overcorrection at light load.
A reliable three phase load calculation is the foundation of safe and efficient electrical design. By applying the correct formulas, validating assumptions, and checking current, kW, kVA, and kVAR together, you can make better decisions for feeder sizing, protection, and system expansion. Use the calculator above for fast estimates and the guide sections for engineering-level validation.